Home Page > High pressure safety valves > > E10
E10
| Tipo : Type : | E10 | do: 10mm | |
|---|---|---|---|
| Omologazione Homologation | PN | Coefficiente efflusso ridotto Low flow coefficient | Campo di taratura Setting range |
| E.D. 2014/68/EU IV Cat.(PED) | 100 | 0,85 | 0,3 - 100,0 bar |
| EAC | 100 | 0,85 | 0,3 - 100,0 bar |
| ATEX Ex II 2 G c (1) | 100 | 0,85 | 0,3 - 100,0 bar |
| ATEX Ex II 2 D c | / | / | / |
| ASME VIII Div.1 | 150 | 0,712 | 1,0 - 106,0 bar |
| Canadian Reg. CRN | 150 | 0,712 | 1,0 - 106,0 bar |
| CONFIGURAZIONE - CONFIGURATION | |||
| Materiale Material |
Ottone Brass |
Mista Ottone-Acciaio inox Mixed Brass-Stainless steel |
Acciaio inox Stainless steel |
| Modelli Model |
Con ghiera | / | Con ghiera |
| With ring nut | / | With ring nut | |
| Senza Ghiera | / | Senza Ghiera | |
| Without ring nut | / | Without ring nut | |
| Con protezione | / | Con protezione | |
| With Protection | / | With Protection | |
| / | / | / | |
| / | / | / | |
| / | / | / | |
| / | / | / | |
| Sedi di Tenuta Seal System |
N.B.R. (Std) -10 / + 100 °C | / | N.B.R. (Std) -10 / + 100 °C |
| E.P.D.M. -50 / + 150 °C | / | E.P.D.M. -50 / + 150 °C | |
| VITON -20 / +200 °C | / | VITON -20 / +200 °C | |
| SILICON -60 / +200 °C | / | SILICON -60 / +200 °C | |
| TEFLON -196 / +250 °C | / | TEFLON -196 / +250 °C | |
| KALREZ -20 / +250 °C | / | KALREZ -20 / +275 °C | |
| / | / | / | |
| Connessione Entrata Inlet Connection |
G.1/2" - 3/4" ISO228 | / | G.1/2" - 3/4" ISO228 |
| R.1/2" - 3/4" EN10226 | / | R.1/2" - 3/4" EN10226 | |
| 1/2" - 3/4" NPT | / | 1/2" - 3/4" NPT | |
| / | / | 1" - 1"1/2 Tri Clamp | |
| / | / | / | |
| / | / | / | |
| / | / | / | |
| Connessione Uscita Outlet Connection |
/ | / | / |
| / | / | / | |
| / | / | / | |
| / | / | / | |
| / | / | / | |
| / | / | / | |
| / | / | / | |
| A richiesta possono essere eseguiti collaudi dai più prestigiosi enti quali: INAIL (area ISPESL), TÜV, RINA, Bureau Veritas, ABS e Lloyd On request tests can be made by the most prestigious societies, such as: INAIL (area ISPELS), TÜV, RINA, Bureau Veritas, ABS and Lloyd Register. |
|||
| Note: (1) No Modello Con protezione / No Model With Protection | |||